General introduction
NAL load break switch and NALF load break switch-fuse combination, are high voltage and high performance load break switch that combines gas pressure arc extinguishing and gas generation arc extinguishing. So far, more than 600,000 units have been installed and put into use around the world.
NALF load break switch- fuse combination has the advantages of load break switch and fuse. Load break switch can break any load current up to its rated breaking current. The fuse and its impact device break
any overcurrent up to the rated short circuit breaking current.
Applications:
The main areas of application of NAL/NALF switch-disconnectors are as:
certificate
ISO 9001, ISO14001
standards
IEC 60625, 62271-105, ANSI C37.20.4, GOST 1T16.3-96, GOST 17717-79, CSA C22.2 No.193
structure
Indoor switch-disconnector type NAL with earthing switch type E
1 - switch disconnector
2 - opening side
3 - closed position
4 - open position
5 - pivot side
6 - closed position
7 - earthing switch
8 - open position
| Rated voltage kV | 12 | 17.5 | 24 | 36 | |
| Rated frequency Hz | 50/60 | ||||
| Rated current A | 400/630/1250 | 630/8 00 |
|||
| Lightning impulse withstand voltage KV | Phase‐phase/phase‐ earth |
75 | 95 | 125 | 170 |
| Across isolating distance |
85 | 110 | 145 | 195 | |
| 1 min power frequency withstand voltage KV | Phase‐phase/phase‐ earth |
42 | 45 | 55 | 80 |
| Across isolating distance |
42 | 60 | 70 | 88 | |
| Rated short circuit making current (peak)KA | 67 | 50 | 50 | 50 | |
| Rated peak withstand voltage KA | 82 | 82 | 82 | 66 | |
| Short time withstand voltage KA/S | 31.5/1 25/2 20/3 |
31.5/ 1 25/2 |
31.5/ 1 25/2 16/3 |
25/2 |
|
| Rated active load breaking current A | 400/630/1250 | 630/8 00 |
|||
| Max. breaking capacity in co‐operation with fuses A | 1600 | 1600 | 900 | 300 | |
| Mainly inductive breaking capacity cosφ= 0.15 A | 16 | 16 | 16 | 16 | |
| Max fuse current A | 125 | 125 | 80 | 40 | |
| Pole distance mm | 150, 170, 210 |
170, 210 |
170*, 235, 275 |
360 | |
| Mechanical life times | More than or equal to 2000 | ||||
| Manual operation, manual operation with shunt, motor operation and motor operation with shunt are optional. |
|||||