Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Electric Type |
Still deciding? Get samples of US$ 1000/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
ZW32 series vacuum circuit breaker + recloser is outdoor distribution equipment with rated voltage 11kv up to 40.5kv, three phase 50HZ. It is mainly used to break and close the power system load current, overload current, shor-circuit current. It is widely used in urban power grid as a section or contact switch, or as a outdoor substation outgoing switch in rural electric power distribution system.
It consists of poles, CT, spring or permanent magnet mechanism and enclosure. Spring mechanism is sealed in the enclosure.
It has multi-protection and functions, such as overload, short circuit, quick break, earthing, reclosing, remote control and remote communication.
Operating mechanism: spring mechanism (manual/ motor ) / permanent magnet
Disconnecting switch: disconnecting at one side or both sides ( if needed)
Optional: CT, zero CT, PT, surge arrester
Control and protection: inrush current controller
Bell type FTU (optional)
Box type FTU (optional)
Installation: pole mounted
Standard
IEC 60056
Features
Item | Unit | Data | |||
Rated voltage | kV | 12 | 24 | 40.5 | |
Rated frequency | Hz | 50/60 | |||
Rated current | A | 630/1250 | 1250,1600,2500 | ||
Rated short circuit breaking current | kA | 20,25 | 25,31.5 | ||
Rated short circuit making current(peak) | kA | 50,63 | 63,80 | ||
Rated short time withstand current (4S) | kA | 20,25 | 25,31.5 | ||
Rated peak withstand current (peak) | kA | 50,63 | 63,80 | ||
Rated operating sequence | O-0.3s-CO-180s-CO | ||||
Mechanical life | times | 10000(spring)/30000(permanent magnetic) | |||
Rated short circuit breaking current breaking times | times | 30 | |||
1min power frequency withstand voltage | Between phases, phase to earth(dry) | kV | 42 | 65 | 95 |
across isolation distance(dry) | kV | 48 | 79 | 118 | |
Between phases, phase to earth(wet) | kV | 34 | 34 | / | |
Lightning impulse withstand voltage | Between phases, phase to earth | kV | 75 | 125 | 185 |
across isolation distance | kV | 85 | 145 | 215 | |
Secondary circuit 1 min power frequency withstand voltage | kg | 2 |
Dimensions
standard packaging:
wooden box
delivery time:
within 20 days
shipping:
sea, air, railway, express
Combining manufacturing experience, new technology and industrial knowledge, TENLEE aims to build advanced power distribution and protection systems.
TENLEE is specialized in manufacturing a comprehensive range of solutions from 12kv to 40.5kv for indoor/outdoor systems: gas insulated switchgears
ring main unit
sf6 free switchgears
vacuum circuit breakers
sf6 circuit breakers
reclosers
load break switches
disconnectors
distribution transformers/power transformers
substations
1. What is the delivery date?
Usually within a month for a HQ.
2. Do you have type tests?
Yes, we have type test in China and we also pass type test in Europe.
3. Do you have other voltage ranges?
Yes, we have 12kv, 24kv and 40.5kv.